General Description Design Professional Notes 1. Owner's/developer's contact information, including Email ✅ ⚠️ N ❌ 2. Magesterial district, tax map, and address, if applicable ✅ ⚠️ N ❌ 3. Utility contact information ✅ ⚠️ N ❌ 4. North arrow on all plan sheets ✅ ⚠️ N ❌ 5. Scale references on all plan sheets ✅ ⚠️ N ❌ 6. Current FW Standards and Specifications have been reviewed for compliance at frederickwater.com ✅ ⚠️ N ❌ 7. Current FW construction notes are on plans ✅ ⚠️ N ❌ 8. All existing easements within planview are shown including deed book and page or instrument number ✅ ⚠️ N ❌ 9. Vicinity map included ✅ ⚠️ N ❌ 10. General, overall utility layout sheet with features labeled is included ✅ ⚠️ N ❌ 11. Current existing water and sanitary sewer infrastructure within planview is shown and described ✅ ⚠️ N ❌ 12. Required on-site FW easements are identified ✅ ⚠️ N ❌ 13. Required off-site FW easements are identified ✅ ⚠️ N ❌ 14. Note has been added to landscape drawings that no trees or shrubs shall be placed on FW easements ✅ ⚠️ N ❌ 15. Note has been added to all applicable sheets that irrigation lines and devices, light poles, transformers, junction boxes, pedestals, other obstacles and all dry utilities shall not be placed on Frederick Water easements; perpendicular irrigation lines and dry utility crossings are permitted with 18" minimum vertical separation ✅ ⚠️ N ❌ 16. Note has been added to all applicable sheets that valves, manholes, ARVs and other Frederick Water surface features shall not be placed in curb and gutter, nor sloped portion of handicapped ramps; contractor shall coordinate locations with the Frederick Water inspector ✅ ⚠️ N ❌ 17. Note has been added to all applicable sheets that retaining walls and their tie backs such as geo grid or other supports shall not be placed in Frederick Water easements ✅ ⚠️ N ❌ 18. Project Acceptance Requirements per FW standards (page 4) have been considered in project phasing ✅ ⚠️ N ❌ 19. Existing site conditions are shown within planview and labeled, i.e. ex. structures, utilities, etc. ✅ ⚠️ N ❌ 20. Master development plan reviewed for compliance and MDP #, date included. Any variance from MDP water or sewer requirements is explained ✅ ⚠️ N ❌ 21. Proffer statement reviewed for compliance and copy included ✅ ⚠️ N ❌ 22. Exceptions to FW requirements are described and justification(s) provided ✅ ⚠️ N ❌ 23. Length of water and sewer lines on private property to be owned by FW kept to minimum ✅ ⚠️ N ❌ 24. Lot numbers, building numbers, and street names are shown on all sheets ✅ ⚠️ N ❌ 25. All plan sheets have been reconciled to reflect the same information ✅ ⚠️ N ❌ 26. Match lines are provided on all applicable sheets ✅ ⚠️ N ❌ 27. Existing FW infrastructure requiring field adjustment where grade changes occur has been shown ✅ ⚠️ N ❌ 28. Existing FW facilities to be removed are noted accordingly; significant items, fire hydrants, valves, etc., are noted to be furnished to FW inspector ✅ ⚠️ N ❌ 29. Ownership of existing and proposed water and sanitary sewer is labeled ✅ ⚠️ N ❌ 30. Continuity of service to adjacent parcels has been considered and easements provided ✅ ⚠️ N ❌ 31. Dry utility layout provided for congested areas ✅ ⚠️ N ❌ 32. FW easements are exclusive; crossings permitted only as necessary ✅ ⚠️ N ❌ 33. Street ownership (VDOT or private) is shown ✅ ⚠️ N ❌ 34. Water and sanitary sewer usage is shown in peak GPM and GPD ✅ ⚠️ N ❌ 35. Plan review fee worksheet is completed and check is included in same envelope ✅ ⚠️ N ❌ Water Description Design Professional Notes 36. Project water system has been modeled and provided and brief summary included on plan ✅ ⚠️ N ❌ 37. Air release has been evaluated and shown ✅ ⚠️ N ❌ 38. FW's water infrastructure has been evaluated and can meet project demands ✅ ⚠️ N ❌ 39. Water meter size(s) are shown ✅ ⚠️ N ❌ 40. Fire line(s) to building show gate valve 10'–20' off building with ownership line; valve is the end of FW ownership ✅ ⚠️ N ❌ 41. Double check valve assembly(s) size and location shown ✅ ⚠️ N ❌ 42. Combined fire and domestic risers are shown as applicable or justification provided ✅ ⚠️ N ❌ 43. Water segments are labeled on plan and profile ✅ ⚠️ N ❌ 44. Sanitary sewer crossings are shown under water lines with min. 18" separation ✅ ⚠️ N ❌ 45. Sanitary lateral crossings have lot number and elevation shown on profile ✅ ⚠️ N ❌ 46. All crossings are labeled including min. 18" separation ✅ ⚠️ N ❌ 47. Connection to existing lines are labeled and include party responsible for field connection ✅ ⚠️ N ❌ 48. Special conditions, service disruption, bypass piping, etc., are clearly detailed and blow-up detail provided ✅ ⚠️ N ❌ 49. Existing and proposed line diameters, pipe types, etc., are shown ✅ ⚠️ N ❌ 50. Water lines shall be CL 52 DIP ✅ ⚠️ N ❌ 51. Water lines under permeable pavers should be minimized ✅ ⚠️ N ❌ 52. Bollards around fire hydrants in truck and other vulnerable areas are shown ✅ ⚠️ N ❌ 53. Applicable FW detail drawings are included ✅ ⚠️ N ❌ 54. Restrained joints in fill areas and 20' onto original ground are reflected ✅ ⚠️ N ❌ 55. Existing FW laterals, services, main stubs, etc., unutilized are shown with details for disconnection and removal ✅ ⚠️ N ❌ 56. Neptune Protectus 3 or Neptune Mach 10 Ultrasonic fire meter including size is shown for private firelines ✅ ⚠️ N ❌ 57. Fire lines are shown as CL 52 DIP and restrained ✅ ⚠️ N ❌ 58. Pipe types are shown on plan and profile for all segments ✅ ⚠️ N ❌ 59. Valves are shown on all branches of tees, crosses, wyes, etc. ✅ ⚠️ N ❌ 60. Minimum 25' pre-blast is shown for main-line stubs labeled ✅ ⚠️ N ❌ 61. Water main stubs have gate valve, MJ cap, full 20' joint of CL 52 DIP and flushing assy shown and labeled ✅ ⚠️ N ❌ 62. Air release and vacuum breaker valves have been evaluated and shown ✅ ⚠️ N ❌ 63. Appropriate FW detail drawings are included ✅ ⚠️ N ❌ 64. Virginia Department of Health's Project Summary Report is completed and included, see http://www.vdh.virginia.gov/content/uploads/sites/14/2016/04/General-Permit-Project-Summary-Report.pdf ✅ ⚠️ N ❌ Sanitary Sewer Description Design Professional Notes 65. Project sanitary sewer system has been modeled ✅ ⚠️ N ❌ 66. FW's sanitary sewer infrastructure has been evaluated and can meet project demands ✅ ⚠️ N ❌ 67. Manhole rim elevations are shown ✅ ⚠️ N ❌ 68. Sewer segments are labeled on plan and profile ✅ ⚠️ N ❌ 69. Water line crossings are shown above sewer min. 18" separation ✅ ⚠️ N ❌ 70. All crossings are labeled including min. 18" separation ✅ ⚠️ N ❌ 71. Connection points are labeled and identify party performing connection ✅ ⚠️ N ❌ 72. Special conditions, service disruption, bypass piping, etc., are clearly detailed ✅ ⚠️ N ❌ 73. Line diameters, pipe types, etc., are shown ✅ ⚠️ N ❌ 74. Sewer lines under permeable pavers should be minimized ✅ ⚠️ N ❌ 75. Applicable FW detail drawings are included ✅ ⚠️ N ❌ 76. Existing FW laterals, services, main stubs, etc., unutilized are shown with details for disconnection and removal ✅ ⚠️ N ❌ 77. Restrained joints in fill areas and 20' onto original ground are reflected ✅ ⚠️ N ❌ 78. Drop connections are noted on plans and profiles; justification is provided ✅ ⚠️ N ❌ 79. Multiple inside drop connections into same manhole have been evaluated and larger manhole is identified ✅ ⚠️ N ❌ 80. Manholes larger than 4' are labeled ✅ ⚠️ N ❌ 81. Deep sewer laterals are noted on plans and profiles ✅ ⚠️ N ❌ 82. Pipe types are shown on plan and profile for all segments ✅ ⚠️ N ❌ 83. Minimum 25' pre-blast is shown for main-line stubs ✅ ⚠️ N ❌ 84. Air release and vacuum breaker valves have been evaluated and shown ✅ ⚠️ N ❌ 85. Appropriate FW detail drawings are included ✅ ⚠️ N ❌ Sanitary Sewer Pump Stations Description Design Professional Notes 86. Show all proposed site improvements ✅ ⚠️ N ❌ 87. Pump station wet well accessible by vactor truck ✅ ⚠️ N ❌ 88. Personnel door accessible to full-size pickup truck (suction lift pumps only) ✅ ⚠️ N ❌ 89. Show and label existing contours ✅ ⚠️ N ❌ 90. Show and label final contours ✅ ⚠️ N ❌ 91. Show proposed utilities, including electrical and telephone services information ✅ ⚠️ N ❌ 92. Show transformer and generator location and dimensions ✅ ⚠️ N ❌ 93. Provide 100-year floodplain elevation and note on PS plan ✅ ⚠️ N ❌ 94. Fence is shown on property line ✅ ⚠️ N ❌ 95. Gently sloping minimum 3' gravel outside fence perimeter ✅ ⚠️ N ❌ 96. Surface water is directed away from pump station lot ✅ ⚠️ N ❌ 97. Paving and stone areas are labeled ✅ ⚠️ N ❌ 98. Gate size is shown and post is min. 1' off pavement ✅ ⚠️ N ❌ 99. Access road provides heavy truck access and slopes no greater than 10% ✅ ⚠️ N ❌ 100. Station information sheets are complete including interim and buildout as applicable ✅ ⚠️ N ❌ 101. Appropriate FW detail drawings are included ✅ ⚠️ N ❌